Vulnerabilities

Unpatched Danfoss Controller Flaw Exposes Supermarket Fridges

Unpatched Danfoss Controller Flaw Exposes Supermarket Fridges

Executive Summary

A critical Danfoss controller flaw, CVE-2026-129713, lets an attacker without a login crash the web server on AK-SM 8xxA refrigeration controllers running software 5.4.0 or earlier and possibly run code on them. Danfoss disclosed it on 20 November 2026. The US Cybersecurity and Infrastructure Security Agency (CISA) followed on 24 November with a CVSS v3 score of 9.8. No patch exists; Danfoss says version 5.5.x will fix it but gives no date. CISA knows of no exploitation. No authority has tied the flaw to the supermarket refrigeration attacks in France and Sweden. The researchers who found it say a pre-login bug remains even with Danfoss’s Strict mode switched on.

What the Danfoss Controller Flaw Affects

The affected range includes the newest software Danfoss ships. Its AK-SM 800A download page lists package 5.4.0, dated November 2026, as the latest release. The Danfoss advisory DSA-2026-12-01 covers every version up to and including 5.4.0.

Installing the current update doesn’t remove the bug.

The AK-SM 800A is Danfoss’s current system manager for supermarket refrigeration, run through a built-in web interface. According to CISA advisory ICSA-26-328-03, the flaw is a stack-based buffer overflow (CWE-121) in a CGI handler that needs no login. A crafted HTTP or HTTPS POST request corrupts memory and restarts the web server. CISA says code execution with the web server’s privileges is possible in theory. Danfoss scores it 9.3 under CVSS v4.

The older AK-SM 800 and AK-SC 355, which Danfoss stopped servicing in 2023 and 2021, sit under a separate advisory, DSA-2026-12-02, on weak or known passwords. Danfoss’s answer there is replacement with the 800A series.

Root-Level Bugs Found in Under an Hour

Carlo Meijer of Dutch firm Midnight Blue reported the flaw to CISA. The firm’s technical write-up says he found six pre-authentication stack overflows in under an hour of manual review of firmware 5.3.2 and that all six were registered together as CVE-2026-129713. Five sit in handlers of the main application, which runs as root. The sixth is in sm_fcgi_app, the gateway that enforces Strict mode, it crashed even with Strict mode on. Midnight Blue showed root code execution on older firmware 3.3.0 and withheld the method. It found no stack canaries or secure boot which it says could let an implant survive a factory reset.

Belgium’s Centre for Cybersecurity (CCB) relayed the research on 12 November and warned that Strict mode does not eliminate the risk.

Interim Advice Rests on Network Isolation

Until 5.5.x ships, Danfoss tells owners to keep units off public IP addresses, allow remote access only through a secure VPN or protected network, set Strict mode and use strong passwords. Version 5.5.x will also remove the option to switch Strict mode off, it has been the default since software 4.0. CISA adds firewalls and separating control systems from business networks.

CISA says the controllers are deployed worldwide but gives no count. Midnight Blue, citing Censys data from 10 November, put internet-reachable Danfoss systems in the hundreds and noted that a sizeable share are probably honeypots.

Swedish Stores Were Hit Three Weeks Earlier

On the night of 2 November, cooling systems at several ICA and Coop stores and at Axfood’s e-commerce and home-delivery warehouse were attacked, according to CERT-SE’s week 45 newsletter. Temperatures at some sites passed 50 degrees and large amounts of food were discarded. CERT-SE did not name the equipment vendor. No authority has said the Danfoss controller flaw was used there or in the French wave that began on 11 October.

CERT-SE’s week 47 newsletter, published on 20 November, the day Danfoss went public, did not mention the advisory. Its newest posts, checked on 26 November included nothing on the CVE.

Danfoss has patched AK-SM 800A flaws three times before, in versions 3.3 (August 2023), 4.2 (March 2025) and 4.3.1 (August 2025).

Release Date and Nordic Exposure Unknown

Danfoss hasn’t said when 5.5.x will ship. No source has published a count of exposed AK-SM 8xxA units in Sweden or the Nordics. CISA’s finding of no known exploitation dates from 24 November.

Strict Mode Has Its Own Pre-Login Bug

Part of Danfoss’s interim advice rests on Strict mode. Version 5.5.x will make the setting permanent. Yet the researcher credited with the CVE crashed the component that enforces it, before any login and with the setting on. Network isolation is the one measure Danfoss, CISA and Midnight Blue all list. Midnight Blue tells owners to inventory controllers reachable through system integrators’ 4G modems, not only their own IP ranges.

References

  1. ICSA-26-328-03: Danfoss AK-SM 8xxA Series
  2. DSA-2026-12-01
  3. Danfoss security advisories
  4. AK-SM 800A Series
  5. Multiple remote code execution vulnerabilities in Danfoss SM-800A
  6. Six New Danfoss Vulnerabilities
  7. NCSC – CERT-SE veckobrev v.45

This post is also available in: Svenska

Erik Berg

Erik Berg is CTO and Principal Security Architect at eBuilder Security, with more than a decade in blue team security operations across the private and public sectors, and a focus on emerging threats including the security risks that come with AI.